Minoprotect 3 and 4 wireless smoke detectors
B.One Service

Minoprotect 3 + 4 radio wireless smoke detector

Explanation of the functions and error messages of your smoke detectors with tips for self-testing and muting in case of false alarms.

Disorders

Should the device trigger a false alarm, first perform a smoke detector test. If a fault is still indicated, inform your contact person or the building manager. Under no circumstances should you open the device yourself. Do not attempt to repair it yourself.

Smoke detector test to check functionality

Before testing, please check that the smoke detector is attached to the base plate. Without this attachment, the smoke detector will be deactivated.

  • If the smoke detector is activated, the red LED should briefly light up once every 46 seconds. This is the normal state.
  • Press the test button briefly once.
  • Don't be alarmed. The alarm is functioning correctly if it emits two short beeps in quick succession and the red LED flashes simultaneously. The alarm should then fall silent and return to its original operating mode.
  • Repeat this process for all other smoke detectors in your home.
  • Regular testing of the detectors is recommended, ideally once a week.
  • Pressing the test button simulates the effect of smoke in the smoke detector.
    It is not necessary to test the devices with real smoke.
Brunata Minol wireless smoke detector Minoprotect 3+4 radio Function overview

Mute your Minoprotect 3 + 4 radio smoke detector

  • In case of an unwanted alarm triggered by excessive kitchen smoke or steam, the smoke detector can be silenced.
  • In such an alarm, the red LED on the detector's housing flashes rapidly.
  • Press the large test button to silence the smoke alarm for approximately 10 minutes.
  • Muting the alarm reduces its sensitivity. However, the alarm is still active!
  • After ten minutes, the smoke detector returns to its normal operating state.

What to do if problems occur?

Should the device trigger a seemingly unfounded alarm or beep occasionally, first test the smoke detector. To do this, press the button in the center. If a fault is still indicated, please inform us immediately.

Or by phone at: 0711 9491-1999

Under no circumstances should you open the device yourself. Do not attempt to repair it yourself. In case of fire, please immediately alert the fire department by calling emergency number 112.

Fault messages and smoke detector signals from the Minoprotect 3 + 4 radio

operation modesound generatorred LEDLED yellow
normal operation A brief flash every 46 seconds – the smoke detector is working correctly.
Alarm testShort sound signals twice in successionBrief flashing twice in succession, simultaneously with the sound emitter
alarm modeShort sound signals at a rhythm of approximately one secondFlashing at a rhythm of approximately one second, simultaneously with the sound signal
Mute mode Flashing at a rhythm of approximately one second
Error modeSee description under Error Signals
DeactivatedWhen the smoke alarm is not yet activated or is deactivated, all sounds and LEDs are switched off.
Error signalssound generatorred LEDLED yellowRequired measure
Battery malfunctionShort sound signal every 46 seconds ¹Two short flashes every 46 seconds ¹ Inform the contact person and arrange for a device exchange.
Measuring chamber contamination2 short sound signals every 46 seconds ¹Two short flashes every 46 seconds ¹ Inform the contact person and initiate customer service.
Test button error Brief flash every 46 secondsBrief flashing every 46 seconds, simultaneously with the red LEDInform the contact person and initiate customer service.
Sound generator defective Two short flashes every 20 seconds ¹Two short flashes every 20 seconds, simultaneously with the red LED ¹Inform the contact person and initiate customer service.
Smoke inlet openings blocked Two short flashes every 20 seconds ¹brief flashing every 20 seconds, simultaneously with the red LED ¹Inspect the device and remove any blockages to the smoke inlets.
 ¹ Fault indicators can be switched off for approximately 65 hours by pressing the test button.

The smoke detector is sounding an alarm. Here's the correct procedure.

Stay calm. Check all rooms for signs of fire.

If you can rule out a fire

  • Activate the mute function by pressing the test button (e.g., with a broom handle). The signal tone will be suppressed for approximately ten minutes.
  • Ventilate the room thoroughly. Once the potential cause has been eliminated by ventilation, the smoke detector will return to normal operation after approximately ten minutes.
  • If the detector continues to emit a beep or visual signals (LED), there is a malfunction. Use the table below to determine the specific malfunction.

If you detect a fire

  • Immediately bring yourself and all other residents to safety.
  • Call the fire department on 112.
  • Only attempt to extinguish the fire if it is contained.
  • Do not attempt to fight a growing fire yourself.

How to use smoke detectors correctly. Here's what you should know.

Smoke detectors detect developing fires early and warn you of the impending danger in time. Therefore, ensure your devices are functioning correctly – for your own safety!

Do not change the installation location:

  • The installation locations for smoke detectors are specified in the State building regulations The regulations for each federal state are binding and described in more detail in the application standard DIN 14676. Therefore, the detectors must not be removed from their original mounting location and installed elsewhere.
  • When changing the use of rooms, for example, if a former study without a smoke detector becomes a children's room, we strongly recommend retrofitting a smoke detector. In this case, please contact your property management company or landlord.

Protect from damage and contamination:

  • Damaged or contaminated smoke detectors can trigger false alarms. See also the adjacent information "Avoiding False Alarms".
  • Contact with aerosols (e.g., canned spray), water, cleaning agents, nicotine deposits, and insect contamination can impair the functionality of the detector.
  • Remove external dirt with a slightly damp cloth. NO Clean with a vacuum cleaner! Dust and lint are best removed with a statically charged duster.

Avoid false alarms:

  • If smoke or dust particles enter the smoke chamber in high concentrations, the smoke detector will trigger an alarm. This can happen during renovation work, for example, when fine dust is generated by drilling or sanding. Painted detectors also lose their functionality. Therefore, ensure that the devices are removed or covered during this time.
  • After completing the work, check the functionality of the detector by performing a function test and verifying the accessibility of the smoke entry openings. If you have temporarily removed the smoke detector, it must be reinstalled in its original mounting location.
  • False alarms can also be triggered if heavy smoke or steam from the kitchen or bathroom enters other rooms equipped with smoke detectors. This can be avoided by, for example, keeping the kitchen door closed while cooking.
  • If an alarm is triggered, the smoke detector can be silenced using the large test button. It is important that you then ventilate your apartment thoroughly.
  • Muting the alarm does not affect its functionality. It will function fully again afterwards.

If a fire should break out, prepare yourself.

  • Every resident should familiarize themselves with the signal tone of the smoke detector so that the signal tone is recognized as such.
  • Discuss the escape route with all residents and walk it together. In an emergency, a practiced escape route can be lifesaving.
  • Escape routes must be kept clear. Therefore, ensure at all times that they are not obstructed and that you are not prevented from quickly leaving the building.
  • Before opening a door in an emergency, carefully test it with your hands (caution: risk of burns!). If the door feels hot, there could be a fire behind it. Keep the door closed and find another escape route. Opening the door could fan the flames and cause air to spread.
  • Don't waste time gathering personal belongings. They can be replaced, your life cannot!
  • Inform all residents and leave the building as quickly as possible.
  • Take refuge in the stairwell.
    • Warn your roommates or neighbors.
    • Leave the house.
    • Choose the Emergency number 112.
  • If the escape route in the stairwell is blocked, remain calm and do not panic.
    • Go back into the apartment and close the apartment door.
    • If possible, seal the gap under the apartment door with a damp blanket or similar material.
    • Choose the Emergency call 112.
    • Wait at the window for the fire department.